PV array capacity, PA stc = 100kW
Eout predicted Predicted AC energy generation (kWh)
PA stc PV array capacity (W)
Yf predicted Predicted final system yield from simulation software (kWh/kW) or (kWh/kWp), also can said the unit is hour
From the simulation software, Eout predicted = 127.8 MWH per annum
Yf predicted = 127800 / 100 = 1278 kWh/kW per annum
Eout expected Expected AC energy generation (kWh)
PA stc PV array capacity (W)
Yf expected Expected final system yield from mathematical formula (kWh/kW) or (kWh/kWp), also can said the unit is hour
From the Step 5 Output Energy >> 5.2.2 Calculate Eout expected, Eout expected = 131.6179 MWH per annum
Yf expected = 131617.9 / 100 = 1316.179 kWh/kW per annum
Eout measured Measured AC energy generation (kWh)
PA stc PV array capacity (W)
Yf measured Measured final system yield from measurement (kWh/kW) or (kWh/kWp), also can said the unit is hour
From the Step 5 Output Energy >> 5.3 Measured AC Output Energy, Eout measured = 133.33 MWH per annum
Yf measured = 133330 / 100 = 1333.3 kWh/kW per annum
Design And Sizing of Grid-Connected Photovoltaic Power System - SEDA Malaysia- 4th Published 2023
Example 7.3
SEDA GCPV Tutorial Design - Nov 2024
3. System performance and evaluation - Question 3