SOLARMAN 200W PV modules and SUNMAN 3.6 inverter are selected.
PV cell temperature range is 20 °C - 75 °C
SUNMAN Inverter Datasheet
SOLARMAN 200W PV Module Datasheet
7. to 10. are temperature coefficients.
VPmax STC Voltage at maximum power of PV module at STC/Maximum power voltage / Voltage at Pmax, VPmax STC/Vmpp/Vmp/Vm (V)
VPmax max Maximum voltage at maximum power of PV module (V)
βVpmax Temperature coefficient for voltage at maximum power (% °C⁻¹ or % K⁻¹).
In most cases, if βVpmax is not given, then assume βVpmax = temperature coefficient of Pmax, γPmax.
Tmod min Lowest module temperature (°C)
Assume 20 °C if not given
TSTC Module temperature at STC (°C), 25 °C
During inverter in ON state, the highest operating module voltage is 30.916V.
Ns max mppt Maximum number of PV modules in series based on maximum voltage at maximum power (units)
Vmax mppt inv Maximum MPPT input voltage of the inverter (V).
Maximum power point of the PV array can't be tracked if inverter input voltage more than this value.
Select "MPP voltage range" for Vmax mppt inv value
Ns max mppt = round down [ 500/30.916 ] = round down [16.17] = 16 units of PV modules
Design And Sizing of Grid-Connected Photovoltaic Power System - SEDA Malaysia- 4th Published 2023
Example 4.4
SEDA GCPV Tutorial Design - Nov 2024