SOLARMAN 200W PV modules and SUNMAN 3.6 inverter are selected.
PV cell temperature range is 20 °C - 75 °C
𝜂cable = 0.97
SUNMAN Inverter Datasheet
SOLARMAN 200W PV Module Datasheet
7. to 10. are temperature coefficients.
VPmax STC Voltage at maximum power of PV module at STC/Maximum power voltage / Voltage at Pmax, VPmax STC/Vmpp/Vmp/Vm (V)
VPmax min Minimum voltage at maximum power of PV module (V)
βVpmax Temperature coefficient for voltage at maximum power (% °C⁻¹ or % K⁻¹).
In most cases, if βVpmax is not given, then assume βVpmax = temperature coefficient of Pmax, γPmax.
Tmod max Highest module temperature (°C)
Assume 75°C if not given
TSTC Module temperature at STC (°C), 25 °C
During inverter in ON state, the lowest operating module voltage is 24.575V.
Ns min mppt Minimum number of PV modules in series based on minimum voltage at maximum power (units)
𝜂cable DC cable efficiency (decimal)
Refer to MS 1837:2018, the highest cable loss is 3%, so assume 100% - 3% = 97% (0.97) if not given
Vmin mppt inv Minimum MPPT input voltage of the inverter (V)
Maximum power point of the PV array can't be tracked if inverter input voltage less than this value. Surrounding temperature rising cause input voltage drop.
Select "MPP voltage range for nominal power" for Vmin mppt inv value
Ns min mppt = round down [ 130/(24.575 * 0.97) ] = round down [5.45] = 6 units of PV modules
Design And Sizing of Grid-Connected Photovoltaic Power System - SEDA Malaysia- 4th Published 2023
Example 4.7
SEDA GCPV Tutorial Design - Nov 2024