PV cell temperature range is 20 °C - 75 °C
JASA 250W PV modules and MICE0.25 micro-inverter are selected
Datasheet JASA PV module
Datasheet MICE family
Ns max mppt = round down [Vmax mppt inv] / [VPmax max]
Ns max mppt Maximum number of PV modules in a string based on the maximum MPPT of micro-inverter
Vmax mppt inv Maximum MPPT voltage of the micro-inverter
VPmax max Maximum voltage at maximum power of PV module
VPmax STC Voltage at maximum power of PV module at STC (V)
VPmax max Maximum voltage at maximum power of PV module (V)
βVpmax Temperature coefficient for voltage at maximum power (% °C^-1 or % K^-1). In most cases, if β_Vpmax is not given, then β_Vpmax shall be approximated to γ_Pmax.
Tmod min Lowest module temperature (°C)
TSTC Module temperature at STC (°C), 25 °C
Ns max mppt = round down [50/30.969] = round down [1.61] = 1 unit
Only 1 PV module shall be connected in series to keep the micro-inverter operating in MPPT mode during the highest operating DC voltage.
Design And Sizing of Grid-Connected Photovoltaic Power System - SEDA Malaysia- 4th Published 2023
Example 5.3