Voc stc = 30 V
PV array configurations: 1 X 13
Voc stc string = Voc stc * Ns
Voc stc string Open circuit string voltage at STC (V)
Voc stc Open circuit voltage at STC of PV modules (V)
Ns Number of series-connected modules (units)
Voc stc string = 30 * 13 = 390 V
Criteria 1 : Voc string measured < Vmax abs inv
Vmax abs inv is maximum absolute input voltage of the inverter (V).
Inverter will be damage if inverter input voltage higher than this value.
Refer to inverter datasheet --> DC input voltage
[Tips] The value of Voc string measured will closed to Voc stc string
Criteria 2 : <Grid voltage> within <Maximum AC voltage range> / <Operating AC voltage Range>
Maximum AC voltage range / Operating AC voltage Range can refer to inverter datasheet --> AC output
Criteria 3 : <Grid frequency> within <Frequency operating range>
Frequency operating range can refer to inverter datasheet --> AC output
Example Connection
Criteria 1 : <Grid voltage> within <Maximum AC voltage range> / <Operating AC voltage Range>
Maximum AC voltage range / Operating AC voltage Range can refer to inverter datasheet --> AC output
Grid voltage should be approximate to value in Step 3.2.
Criteria 2 : <Grid frequency> within <Frequency operating range>
Frequency operating range can refer to inverter datasheet --> AC output
Grid frequency should be approximate to value in Step 3.2.
Criteria 3 : <DC string voltage from PV array> within <MPPT voltage range>
MPPT voltage range can refer to inverter datasheet --> DC input
Criteria 4 : <DC string current from PV array> below <Maximum DC current per MPPT>
Maximum DC current per MPPT can refer to inverter datasheet --> DC input
SEDA GCPV All Practical Manual
Test and Commissioning - System 1