SOLARMAN 200W PV modules and SUNMAN 3.6 inverter are selected.
PV cell temperature range is 20 °C - 75 °C
SUNMAN Inverter Datasheet
SOLARMAN 200W PV Module Datasheet
7. to 10. are temperature coefficients.
Ns max pv Maximum number of PV modules in series based on maximum system voltage of the PV module (units).
Voc max Maximum open circuit voltage of the PV module (V)
Vsys max Maximum system voltage of the PV modules/Maximum System Voltage from PV datasheet (V).
This value is maximum voltage limit allowed of the entire PV array for this model of PV module.
If more than this value may cause PV modules have safety risk (overheating etc.)
Select maximum one is multple values are provided.
βVoc_v Temperature coefficient for open circuit voltage (V°C⁻¹ or VK⁻¹)
βVoc = (-0.1368 VK⁻¹ / 37.47 V) *100% = - 0.3651%K⁻¹
Can direct take value in Step 2 Maximum Absolute Input Voltage >> 3.2 Calculate Voc max
Voc STC Open circuit voltage of the PV module at STC (V)
βVoc Temperature coefficient for open circuit voltage (% °C⁻¹ or % K⁻¹)
Tmod min Lowest module temperature (°C)
TSTC Module temperature at STC (°C), 25 °C
During inverter in OFF state, the highest open circuit module voltage is 38.154 V.
Ns max pv = round down [1000 / 38.154] = round down [26.21] =26
The maximum number of PV modules in series that shall not exceed the maximum system voltage of the PV modules is 26 units.
Design And Sizing of Grid-Connected Photovoltaic Power System - SEDA Malaysia- 4th Published 2023
Example 4.5
SEDA GCPV Tutorial Design - Nov 2024