Authority set 4kW as the maximum allowable power transfer for a single-phase NEW customer, Pout max.
No power clipping, f1 = 1.11
With power clipping, f1 = 1.20
SUNMAN Inverter Datasheet
SOLARMAN 200W PV Module Datasheet
7. to 10. are temperature coefficients.
PA STC PV array capacity (W)
f1 DC/AC ratio (decimals)
Pnom inv Nominal power of the inverter/ Apparent power (only if no active power output provided) (W)
Nt ac pwr Total number of PV modules based on AC power limit (units)
Pmax STC Peak power of PV module at STC (W)
f1 < 1.11 No power clipping
f1 > 1.11 With power clipping
During calculation assume f1 = 1.11, if new f1 is provided also using 1.11 in calculation.
Pout max Maximum allowable AC power limit injected into the gird by the authority, ≠ PmaxSTC (W)
f1 DC/AC ratio. Typically, 1.11 (decimal)
No power clipping --> 1.11 > f1
With power clipping --> 1.11 < f1
Criteria
Step 2.3 Calculate Pnom inv
Select 40°C in Malaysia because maximum ambient temperature in Malaysia is 35°C
2. Maximum inverter power output/ Maximum active power of inverter/maximum apparent power <= Pout max
3. New f1 is closed to f1 that given (if any)
No power clipping --> 1.11 > f1
SUNMAN 4.0
Nominal power = 4000 W > 3963.964 W
Apparent power = 4000 VA = 4000 W
New f1 = (22*200) / 4000 = 1.10 (aprroximate to 1.11 given by question)
With power clipping --> 1.11 < f1
SUNMAN 3.6
Nominal power = 3680 W < 3963.964 W
Apparent power = 3680 VA < 4000 W
New f1 = (22*200) / 3680 = 1.19 (aprroximate to 1.20 given by question)
Design And Sizing of Grid-Connected Photovoltaic Power System - SEDA Malaysia- 4th Published 2023
Example 3.7
Example 4.1
Example 4.2
SEDA GCPV Tutorial Design - Nov 2024
1. Dimensioning of PV array - Question 8
2. Sizing with string or central inverter - Question 1