PV array capacity, PA stc = 100kW
No power clipping
CF predicted Predicted capacity factor(decimal)
Eout predicted Predicted AC Output Energy (Wh)
CF expected Expected capacity factor(decimal)
Eout expected Expected AC Output Energy (Wh)
CF measured Measured capacity factor(decimal)
Eout measured Measured AC Output Energy (Wh)
f1 DC/AC ratio (decimals)
PA stc PV array capacity (W)
D Number of days (d)
365 days if it's yearly analysis
30 days if it's monthly analysis
From Step 5 Output Energy :
Eout predict = 127.8 MWH per annum
Eout expected = 131.6179 MWH per annum
Eout measured = 133.33 MWH per annum
Pmax inv Maximum rating of inverter (kVA)
Design And Sizing of Grid-Connected Photovoltaic Power System - SEDA Malaysia- 4th Published 2023
Example 7.7
SEDA GCPV Tutorial Design - Nov 2024
3. System performance and evaluation - Question 3