SOLARMAN 200W PV modules and SUNMAN 3.6 inverter are selected.
PV cell temperature range is 20 °C - 75 °C
SUNMAN Inverter Datasheet
SOLARMAN 200W PV Module Datasheet
7. to 10. are temperature coefficients.
Voc STC Open circuit voltage of the PV module at STC (V)
Voc max Maximum open circuit voltage of the PV module (V)
βVoc Temperature coefficient for open circuit voltage (% °C⁻¹ or % K⁻¹)
Tmod min Lowest module temperature (°C)
Assume 20°C if not given.
TSTC Module temperature at STC (°C), 25 °C
βVoc_v Temperature coefficient for open circuit voltage (V°C-1 or VK⁻¹)
βVoc = (-0.1368 VK⁻¹ / 37.47 V) *100% = - 0.3651%K⁻¹
During inverter in OFF state, the highest open circuit module voltage is 38.154 V.
Ns max abs Maximum number of PV modules in series based on maximum open circuit voltage (units)
Vmax abs inv Maximum absolute input voltage of the inverter (V).
Inverter will be damage if inverter input voltage higher than this value.
Refer to inverter datasheet --> DC input voltage
Ns max abs = round down [ 600 / 38.154] = round down [15.73] =15
The maximum number of PV modules in series that shall not exceed the maximum absolute input voltage of the inverter is 15 units.