Target power output of GCPV array system, Pout target array = 4.0kW
KSO-340 PV modules and PZ370 DC power optimiser are selected
Datasheet KSO-340 PV module at STC
Datasheet PZ DC power optimiser
Datasheet of inverters
Ns abs opt = round down [Vmax abs inv] / [Vmax out opt]
Ns abs opt Maximum number of PV modules in series based on the maximum open circuit voltage of DC power optimiser
Vmax abs inv Maximum abolute input voltage of the inverter
Vmax out opt Maximum output voltage of DC power optimiser
Ns abs opt should lies between recommended string length of DC power optimiser.
Nt opt = round [Pout target array] / [PA max]
Nt opt Total number of DC power optimiser
Pout target array Target power output of GCPV array system
PA max Maximum power output of solar panel at standard test condition (STC)
Nt opt = round [4000 / 340] = round [11.76] = 12 units of DC power optimisers
Ptot opt = Nt opt * Pnom opt
Ptot opt Total output power if DC power optimiser
Pnom opt Power rating of DC power optimiser (W)
Select inverter which its maximum input DC power > Ptot opt
Ptot opt = 12 * 370 = 4440 W
SE3000H inverter is selected because its maximum input DC power is 4650W (> Ptot opt = 4440 W)
Ns abs opt = round down [480 / 60] = 8 units
Ns abs opt lies between recommended string length of DC power optimiser (6...25)
Number of Strings of DC Power Optimisers = round up [Nt opt / Ns abs opt]
Number of Strings of DC Power Optimisers = round up [12 / 8] = round up [1.5] = 2 strings
If Number of Strings of DC Power Optimisers = n,
String [n-1]: [Nt opt / n] units of DC power optimisers
String [n]: [Nt opt / n] units of DC power optimisers
Nt opt / n = 12 / 2 = 6
String 1: 6 units of DC power optimisers
String 2: 6 units of DC power optimisers
Parray_stc = Nt opt * PA max
Parray_stc Final PV array capacity
Parray_stc should > Pout target array
Parray_stc = 12 * 340 = 4.08kW (> Pout target array = 4 kW)
Design And Sizing of Grid-Connected Photovoltaic Power System - SEDA Malaysia- 4th Published 2023
Example 6.5