MICE0.25 micro-inverter are selected
20 units PV modules are installed
Datasheet MICE family
Number of PV Modules Branch = Total number of PV Modules / Maximum number of micro-inverter units per branch
From micro-inverter datasheet, maximum number of units per branch = 10
Number of PV Modules Branch = 20 / 10 = 2 branches
Number of PV modules per branch = Total number of PV Modules / Number of PV Modules Branch
Number of PV modules per branch = 20 / 2 = 10 units of PV modules per branch
If Number Of PV Modules Branch = n,
Branch [n-1]: [Number of PV modules per branch] units PV modules and [Maximum number of micro-inverter units per branch] units of micro-inverters
Branch [n]: [Number of PV modules per branch] units PV modules and [Maximum number of micro-inverter units per branch] units of micro-inverters
Branch 1: 10 units PV modules and 10 units of micro-inverters
Branch 2: 10 units PV modules and 10 units of micro-inverters
Design And Sizing of Grid-Connected Photovoltaic Power System - SEDA Malaysia- 4th Published 2023
Example 5.5